Kitchen fire suppression in Georgia

Facts checked 2026-11-15.

Fire suppression piping and a fitting running along the baffle filters inside a hood
Suppression piping inside a hood, above the filters.

The system over your cooking line that sprays when a fire starts must be installed and serviced by a firm licensed in Georgia. Submit a request for a new system, a change or an inspection on Commercial Kitchen Connect, and it goes to fire suppression companies, licensed where the law requires it.

What the state requires

Rule 120-3-3 calls for an approved automatic fire-extinguishing system on each required commercial kitchen exhaust hood and duct. It adopts NFPA 17A, the wet chemical standard, in its 2024 edition, effective May 27, 2025. The 2013 edition applied before. If your system was installed under an older edition, ask the fire marshal how that is treated.

Who may do the work

Under Rule 120-3-23 the firm is licensed and the technician is permitted. Each technician is employed by a licensed firm and carries a kitchen technician permit. The firm must be a Georgia corporation with liability insurance of at least $1,000,000.

Some licenses cover less than others. A firm licensed on one manufacturer's certification may work only on that maker's systems. If your hood has a particular brand, ask the company whether its license reaches that brand.

Get prices for this job. Send one request and pick how many local companies quote it.

Get quotes

Reading the blue tag

A suppression system carries a light blue tag, 3 by 5.5 inches. It shows:

Each service brings a new tag, and only the latest stays on the system. On a battery-powered control panel, the tag and battery together show when the battery is due for replacement.

When the system is down

The state's NFPA 17A changes forbid running cooking equipment while the system protecting it is impaired or not operating. A firm that finds a system short of its design capacity tags it as non-compliant and reports to the fire authority. Under the NFPA 96 changes, the owner then notifies the fire authority in writing within 24 hours.

Records

Hold each maintenance report for three years after the next maintenance of that type. The licensed firm keeps its own records for at least two years. A folder in the kitchen office does the job.

Where plans are filed

The Safety Fire Commissioner's office reviews safety fire plans for certain building types through its portal. A restaurant's plans might go to the state, to the local fire marshal, or to both, so ask the marshal about your address. Gwinnett County names suppression systems among its permits, and Atlanta schedules fire protection inspections.

Before you call

Collect what a company will want to know. Write down the system's brand and age if you have them, the appliances under the hood and any you plan to move or add. When an appliance shifts under a hood, the nozzles may point at the wrong spot, which makes a change to the line a job of its own. Keep the last tag and report within reach.

Questions

Who may service a restaurant suppression system in Georgia?

A company holding a Safety Fire Commissioner license under Rule 120-3-23, using a technician who has a kitchen technician permit.

What color is the tag on a kitchen suppression system?

Light blue, 3 by 5.5 inches. It lists the firm's license number and the technician's permit number.

How long must a kitchen keep suppression system records?

Three years after the next maintenance of that type that NFPA 17A calls for.

May a kitchen keep cooking while the system is impaired?

No. The state's NFPA 17A changes say cooking equipment may not run while the protecting system is impaired or not operating.

Sources

  1. Georgia Rule 120-3-3, State Minimum Fire Safety Standards (OCI PDF)
  2. Georgia Rule 120-3-3-.04, adopted standards and history
  3. Georgia Rule 120-3-23-.06, firm licenses for kitchen systems
  4. Georgia Rule 120-3-23-.07, technician permits for kitchen systems
  5. Georgia Rule 120-3-23-.13, service and records
  6. Georgia Rule 120-3-23-.14, tags
  7. OCI safety fire plan review
  8. OCI licensed professionals search