Georgia's extinguisher rules show up on the wall: the tag, the mounting height and the place where the unit hangs. If one needs service or a replacement, send the request through Commercial Kitchen Connect and it goes to a fire extinguisher company, licensed where the law requires it.
The standard behind the tag
Rule 120-3-3 adopts the 2022 edition of NFPA 10, the standard for portable extinguishers. The 2018 edition applied before it, and the switch took effect on May 27, 2025. The state adds conditions of its own. Anyone who maintains or recharges extinguishers needs a license or permit under Title 25, Chapter 12 of the Georgia code. A unit of 40 pounds or less must have its top no more than 48 inches above the floor.
Placing the Class K unit
A kitchen with fryers normally keeps a Class K extinguisher near the cooking line. Under Georgia's fire code changes, it hangs 5 to 10 feet from the manual release of the hood suppression system, next to the sign that explains the operating sequence. If a remodel moves the hood, move the extinguisher too.
Get prices for this job. Send one request and pick how many local companies quote it.
Get quotesWho can service a unit
Under Rule 120-3-23 the firm holds a license and each technician holds a permit. The firm has to be a current Georgia corporation carrying at least $1,000,000 in liability insurance and a qualifying certification, and it files sample tags with the State Fire Marshal. Technicians work only for a licensed firm. The Commissioner can inspect a firm with or without warning.
What the yellow tag shows
Georgia extinguisher tags are light yellow and measure 3 by 5.5 inches. They list the firm's license number, the technician's permit number and the date of the last service. Where a hydrostatic test applies, its due date is listed as well. If a tag is missing, faded or out of date, contact the firm that last serviced the unit.
The six-year maintenance label is something else. It is a blue metallic decal that destroys itself when peeled off, and it carries the same two numbers.
A walk-through before the inspector
- Is each unit on its bracket, with the pin and seal intact?
- Is the top of every unit of 40 pounds or less at 48 inches or below?
- Is each tag dated, and does it show both the firm's license number and the permit number of the technician?
- Is the Class K unit within 5 to 10 feet of the system's manual release?
- Can anyone reach each unit without moving stock?
Items two to four come from state rules. The fire marshal can tell you what else it looks for.
If a unit fails
An extinguisher that is not maintained under NFPA 10 gets a non-compliant tag from the firm, which also reports to the fire authority, typically the local fire marshal. Save your own copy of every service report.
Questions
What color is an extinguisher tag in Georgia?
Light yellow, 3 by 5.5 inches. Kitchen suppression systems use a light blue tag in its place.
What is the maximum mounting height for an extinguisher in Georgia?
Under Georgia's NFPA 10 changes, the top of a unit weighing 40 pounds or less may be no higher than 48 inches above the floor.
Where should a Class K extinguisher hang in a Georgia kitchen?
It goes 5 to 10 feet from the manual release of the hood suppression system, close to the operating sequence sign.
Who may recharge a restaurant extinguisher in Georgia?
A firm licensed under Rule 120-3-23 that uses a permitted technician. The Safety Fire Commissioner issues both the license and the permit.
Sources
- Georgia Rule 120-3-3, State Minimum Fire Safety Standards (OCI PDF)
- Georgia Rule 120-3-3-.04, adopted standards and history
- Georgia Rule 120-3-23-.04, extinguisher firm licenses
- Georgia Rule 120-3-23-.05, extinguisher technician permits
- Georgia Rule 120-3-23-.13, service and records
- Georgia Rule 120-3-23-.14, tags
- OCI licensed professionals search